Product: ISOMETER® IR420-D6  
 
  Bender GmbH
 
IR420_D6
 

The offline monitor of the IR420-D6 series is designed to monitor the insulation resistance of loads in the de-energized state. These loads, usually temporarily operated or de-energized most of the time, e.g. fire extinguisher pumps, slide valve drives etc are supplied from TN, TT or IT systems. During the shut-down periods, hohwever, humidity or other effects may cause insulation faults in the wiring or the loads which may go undetected. Switching the device on may then lead to the tripping of the protective device or may even result in motor fires and the device cannot be operated. In combination with a coupling device, the Iso­meters can also be used for higher voltages.

Characteristics of ISOMETER® IR420-D6

  • Insulation monitoring for de-energised TN, TT and unearthed systems AC, 3(N)AC and DC
  • Nominal voltage extendable via coupling device
  • Two separately adjustable response values 100 kΩ…10 MΩ
  • LEDs: Power On LED, LEDs Alarm 1, Alarm 2 for signalling insulation faults
  • Combined test/reset button
  • Two separate alarm relays with one changeover contact each
  • Fault memory behaviour, selectable
  • Push-wire terminal (two terminals per connection)
  
top sitemap recommended resolution: 1024x768 last update: 19.09.2021.