ISOMETER® isoPV425 with coupling device AGH420
Insulation monitoring device for unearthed DC circuits (IT systems)
for photovoltaic installations up to 3(N)AC, AC 690 V/DC 1000 V
Product description
The ISOMETERR of the isoPV425 series monitors the insulation resistance of unearthed AC/DC main circuits (IT systems) with nominal voltages of 3(N)AC, AC, AC/DC 0…690 V or DC 0…1000 V.
DC components existing in AC/DC systems do not influence the operating characteristics.
A separate supply voltage allows deenergised systems to be monitored as well. The maximum permissible system leakage capacitance is 500 μF.
Application
• AC, DC or AC/DC main circuits
• Solar systems with directly connected inverters
• Solar systems with high system leakage capacitances
• Solar systems with high but slow voltage fluctuations
• Systems including switch-mode power supplies
Device characteristics
• Monitoring for unearthed AC and DC systems with galvanically connected rectifiers or inverters
• Measurement of the nominal system voltage (r.m.s.) with undervoltage and overvoltage detection
• Measurement of DC voltages system to earth (L+/PE and L-/PE)
• Automatic adaptation to the system leakage capacitance up to 500 μF
• Automatic device self-test with connection monitoring
• Selectable start-up delay, response delay and delay on release
• Two separately adjustable response value ranges of 1…500 kΩ (Alarm 1, Alarm 2)
• Alarm signalling via LEDs (AL1, AL2), a display and alarm relays (K1, K2)
• N/C operation or N/O operation selectable
• Measured value indication via multifunctional LCD
• Fault memory can be activated
• RS-485 (galvanically isolated) including the following protocols:
– BMS interface (Bender measuring device interface) for data exchange with other
Bender components
– Modbus RTU
– isoData (for continuous data output)
• Password protection to prevent unauthorised parameter changes |